If it fails: the first hour
What the site contact should do before the technician arrives.
- Identify the specific fixture or exit sign that failed and its location on the egress path
- Post temporary battery-powered lighting or signage if the fixture cannot be repaired immediately
- Contact a licensed electrician or life safety contractor for same-day repair
- Document the failure and temporary measure taken for the facility's compliance record
What fails
What a service call includes
- Performing the required 30-second monthly functional test and documenting the result
- Conducting the annual 90-minute full discharge test on battery-powered units
- Testing illuminated and non-illuminated exit signs for visibility and lamp or LED function
- Replacing failed batteries, lamps, or LED modules found during testing
- Checking spacing and coverage of egress path lighting against code-required foot-candle levels
- Inspecting self-testing units for fault codes and confirming actual test completion, not just a passing indicator light
- Providing a written, dated test log for the facility's life safety compliance file
Preventive checklist
The items a maintenance program should carry for this system. Build a combined checklist across systems with the checklist builder.
Quarterly
- Perform the required monthly functional test and log the result
- Visually check exit signs for burned-out lamps or LED segments
Annual
- Conduct the full 90-minute battery discharge test required by NFPA 101
- Replace batteries approaching the end of their rated service life, typically every 3 to 5 years
- Review the full year's test log for gaps in monthly documentation
What it costs
| item | typical range | what moves it |
|---|---|---|
| Emergency light and exit sign inspection, per unit | $15 to $40 | Lower end applies to bulk testing across many units in one visit. |
| Battery replacement, per unit | $30 to $100 | Sealed lead-acid batteries are common and generally at the lower end; specialty batteries cost more. |
| LED exit sign replacement | $50 to $150 installed | Replacing an older incandescent sign with an LED unit reduces long-term energy and bulb replacement cost. |
| Annual compliance testing program, small building | $300 to $1,200 per year | Covers scheduled monthly and annual testing across all emergency lighting and exit signs in the facility. |
| Egress lighting gap correction, added fixture | $200 to $600 per fixture | Includes fixture, wiring to the emergency circuit, and installation labor. |
National ranges. Local labor, access, after-hours timing and materials move them. Multi-site programs usually price below one-off calls.
When this is an emergency
A completely dark egress path or a non-functioning exit sign discovered outside a scheduled test counts as an emergency because it is a direct life safety gap that needs same-day correction.
How to choose a provider
- Confirm the provider tests to NFPA 101 requirements, including both monthly and annual test intervals
- Ask how self-testing units are verified, since a passing indicator light does not always mean a full test completed
- Request a sample test log to see the level of documentation provided after each visit
- Ask about battery replacement policy, including whether aging batteries are flagged proactively before failure
- Confirm the provider can perform same-day emergency repairs when a unit fails outside the testing schedule
Questions
How often does emergency lighting need to be tested by code?
NFPA 101 requires a functional test of at least 30 seconds monthly and a full 90-minute discharge test annually for battery-powered emergency lighting and exit signs.
What happens if emergency lighting fails its 90-minute test?
The unit needs repair or battery replacement and should be retested to confirm it meets the full duration; a failed unit found during testing is a code deficiency that requires correction, not just documentation.
Are exit signs required to be illuminated at all times?
Yes, exit signs must be continuously illuminated, either by normal power or by internally illuminated or photoluminescent means, and remain visible during a power outage.
Who is responsible for emergency lighting compliance in a commercial building?
The building owner or the tenant, depending on the lease terms, is generally responsible for maintaining and testing emergency lighting to meet local fire code and NFPA 101 requirements.